Home
:
Telecom Products
:
Máquinas de fusión
por empalme
SMPS - Sistemas de Fuentes de alimentación
XL
Telecom & Energy Ltd., Leaders in manufacturing of Telephone
Jointing Kits is bringing its expertise to manufacture Switch
Mode Power supply systems in 48V in modules of 25A &
100A for powering the telecommunications networks.
XL POWERPLANT
The XL POWERPLANT has micro-controller-based modules and
rectifier racks for digital control and flawless performance.
Its architecture allows for easy enhancement of installed
capacity by merely adding the required number of modules/racks.
It is a space-saving model and occupies less floor area
than Thyistor-based chargers. The XL POWERPLANT can be easily
handled since it weighs less than conventional systems but
has higher efficiency and a higher power factor which, in
the long run, contribute to savings in running costs.
It has lower MTTR contributing to substantial reduction
in breakdown time achieved by on-line replacement of module
without switching off total systems and allows for parallel
operation of all modules in all racks.
Features
- Micro Controller Based State of the art Technology
- Compact Design with SMD Components and Higher Operating
Frequency
- Modular construction
- Low volume to Power ratio
- Low weight to power ratio
- High efficiency/ High power factor
- Easy future expansion
- Low MTTR
- High MTBF
Rectifier Rack Features
| Switchgear &
Protection |
- MCB in battery negative path
- Battery low voltage disconnect
- Contractor to disconnect loads
- From battery
|
| Controllers |
Push buttons based
on Micro controllers |
| Indications
(LED) |
|
| Alarm
(audio-visual) |
- Module fall
- Mains fail
- Phase fail
- Battery low
- System overload
- AC under / over voltage
- Load voltage high / low.
- Temp. Comp. Fail
|
| Cable
entry |
From
top
|
| Operating
Temperature |
50
degree C (maximum) |
| Ventilation |
Natural
air cooling/ Forced |
| Paint
Shade |
Beige
/ Customize
|
| Protection
grade |
IP
20 |
| Meters |
Menu
driven LCD display for monitoring Input voltage, Output
voltage & Output currents. |
Technical Specifications for SMPS
Rectifier Module
| Type |
SP-48-25 TP-48-100 |
| DC Output voltage |
Nominal: 48V Adjustable
43-58V |
| Output
Current |
25
A 100A
|
| Input
Supply |
230V
1 Phase
2 Wire
|
400V
3 Phase
3 Wire
|
| Input
Voltage Variation |
150
to 275V |
320
to 480V |
| Input
Current at full load |
11A at 150V,
6A at 275V
|
12.5A at 320 V and
8.5 A at 480V
|
| Input
Frequency |
Nominal
50Hz
Permissible variation 45Hz to 65Hz |
| Static
Line Regulation |
+or-
0.1% of set value |
| Static
Load Regulation |
+ or
0.5% of set value |
|
Dynamic Response
Ripple
|
+ or
0.5% for 25-100% load variations
Recovery time of 20 millisecs.
<300mV max. peak to peak without Battery |
|
Psophometric
Noise
|
<2mV max. at 800 Hz with battery
<4mV max. at 800 Hz without battery
|
| Efficiency |
>90%min.
at nominal I/O and at 100% load |
| Power
Factor |
0.95
min. at nominal input and output load between 75
100% |
| Audible
Noise |
60dB
max. under all operating conditions |
| Short
Circuit Capability |
Short
Circuit at output can be sustained indefinitely |
| Temperature
Compensation |
Slope
adjustment between 1-10mV/0C/cell. |
| Switch
Gear |
MCB
at Input and Output |
| Protections |
- AC Input high
- AC Input low
- DC Output high
- Overload / Short Circuit
- High Temperature
- Input surges
- Phase fail
- Soft start facility
|
| Indications |
Main ON
Float Mode
Charge
|
| Alarm
(visual) |
- DC output over voltage
- DC output under voltage
- DC output overload
- Fan fail (for forced cooling)
|
| Operating
temp. |
50
degree C (maximum) |
| Ventilation |
Forced
air cooling / Natural air cooling |
| Paint
shade |
Beige
[ Epoxy based]/Customize |
| Protection
grade |
IP
20 |
| Display |
Menu
driven 7 segment LCD Display |
| Dimensions
(H)
In mm (W)
(D)
Weight (Kgs)
|
360
150
280
10
|
160
600 Approx.
440
25
|
System Configuration
| No.
of Modules |
Varies |
| Supervisory
Control unit |
One |
| Standard
Features |
Metering
panel, Input, Output and Busbar terminals
|
| Ultimate
capacity |
150A
/ 200A / 300A/ 1000A / 1500A/ 2000A/ 2500A/ 3000A
For modules of 25A / 100A respectively.
|
| Construction |
Multi
Rack Systems
|
| |
The
required number of modules can be added to arrive at
the Ultimate Capacities. |